Wire Size Calculator

Enter the load, the voltage, the one-way run length and the conditions in the raceway, and this calculator returns the minimum conductor by ampacity, the minimum by voltage drop, and which of the two actually governs. On long runs it is almost always voltage drop.

120 or 240 residential, 208 or 480 commercial three-phase.

Panel to load, measured one way. The calculator doubles it for the return path.

30 °C is the table baseline. An attic in summer is 50 °C or more.

Neutrals on a balanced multiwire circuit do not count. Grounds never count.

3% for a branch circuit, 5% total from the service to the load.

Conductor size required
6 AWG
copper, governed by voltage drop
Design current
40.0A
Minimum by ampacityderating factor 1.00 — 1.00 ambient × 1.00 conductor count
8 AWG
Minimum by voltage drop3.0% of 240 V is 7.2 V over 120 ft
6 AWG
Actual voltage drop at that size1.97% — load sees 235.3 V
4.72V
Derated ampacity of that conductor65 A at 75 °C before derating
65.0A

What this figure includes

Ampacities are the 75 °C column of NEC Table 310.16 for conductors in a raceway, with the ambient and conductor-count adjustments applied. It assumes terminations rated 75 °C, a continuous load already included in the figure you enter, and a single non-paralleled run. It does not size the overcurrent device, the equipment grounding conductor or the neutral, apply the continuous-load 125 percent factor, handle motor or welder circuits, check conduit fill, or account for harmonic loading. Have a licensed electrician confirm the design against your adopted code edition.

How this is calculated

Two independent constraints

Sizing a conductor is not one calculation. It is two, run separately, and the larger answer wins.

Ampacity keeps the wire from overheating. Current through resistance makes heat, and the insulation has a temperature rating it must not exceed. NEC Table 310.16 lists how much current each size can carry — 50 A for 8 AWG copper in the 75 °C column, 65 A for 6 AWG, and so on. Exceed it and the insulation cooks, slowly, inside a wall.

Voltage drop keeps the load working. Every foot of conductor has resistance, and current through it consumes voltage that never reaches the equipment. Nothing overheats; the motor just runs hot and slow, the lights dim, the heater underperforms, and the electronics reset. It is a performance problem, not a fire problem, which is why the NEC treats it as an informational note (210.19(A) and 215.2(A)) rather than a hard rule in most cases.

The formulas

Ampacity check: table ampacity × ambient factor × conductor-count factor ≥ load current.

Voltage drop, single phase: VD = 2 × K × I × L ÷ circular mils

Voltage drop, three phase: VD = 1.732 × K × I × L ÷ circular mils

Where K is 12.9 for copper and 21.2 for aluminium, I is amps, and L is the one-way length in feet. The 2 in the single-phase version accounts for the return path — the current has to come back. Circular mils come from Chapter 9, Table 8: 16,510 for 8 AWG, 26,240 for 6 AWG, 41,740 for 4 AWG.

A worked example

A 40 A load at 240 V single phase, copper, 120 ft one way, 30 °C, three conductors in the raceway, 3% drop allowed.

By ampacity: derating is 1.0 × 1.0 = 1.0, so we need 40 A of table ampacity. 8 AWG copper carries 50 A at 75 °C. 8 AWG passes.

By voltage drop: allowed drop is 3% of 240 = 7.2 V. - 8 AWG: (2 × 12.9 × 40 × 120) ÷ 16,510 = 123,840 ÷ 16,510 = 7.50 V, which is 3.13%. Fails, barely. - 6 AWG: 123,840 ÷ 26,240 = 4.72 V, which is 1.97%. Passes.

Governing size: 6 AWG, one size larger than ampacity alone would have told you. This is the entire point of the exercise, and it is what people forget.

On long runs, voltage drop always wins

Ampacity does not care how long the run is. Voltage drop is directly proportional to it. Double the distance and you double the drop, so beyond roughly 100 feet the drop calculation starts overtaking ampacity, and past 150 feet it governs almost every time.

This is why a detached garage, a well pump, a dock, a barn or a landscape lighting run needs a conductor that looks absurdly oversized for its breaker. A 20 A circuit 250 feet out to a shed on 12 AWG loses over 9% of its voltage at full load. The breaker will never trip and the wire will never get warm — the tools out there will just run badly and the motors will die early.

The working guideline, from the informational notes: 3% on a branch circuit, and 5% total from the service to the furthest outlet, feeder and branch combined. Budget it as two halves — 2% on the feeder, 3% on the branch — rather than spending it all in one place.

Derating, which cuts the other way

The table ampacity assumes a 30 °C ambient and no more than three current-carrying conductors in the raceway. Break either assumption and you multiply the ampacity down:

  • Ambient: 0.88 at 40 °C, 0.75 at 50 °C, 0.67 at 55 °C on the 75 °C column. Attics, rooftops and boiler rooms routinely hit these, and rooftop conduit in the sun gets an additional adder.
  • Conductor count: 0.8 for four to six current-carrying conductors, 0.7 for seven to nine, 0.5 for ten to twenty. Grounding conductors never count; the neutral of a balanced multiwire branch circuit does not count either, but the neutral of a circuit serving significant nonlinear load does.

The two factors multiply. Six conductors in a 45 °C attic gives 0.8 × 0.82 = 0.66 — a 6 AWG copper conductor's usable 65 A becomes 43 A.

What this does not decide

The breaker. Overcurrent protection is a separate selection, and NEC 240.4(D) caps 14 AWG at 15 A, 12 AWG at 20 A and 10 AWG at 30 A no matter what the ampacity table says. Continuous loads — anything running three hours or more — get sized at 125 percent. Motors, welders, air conditioners and services all have their own articles. Use this to understand the trade-off, then have the design confirmed by someone licensed to sign it.

Frequently asked questions

What size wire do I need for a 50 amp circuit?
Six AWG copper carries 55 A at 75 °C and 8 AWG carries 50 A, so 8 AWG copper or 6 AWG aluminium is the ampacity answer at standard conditions. Beyond about 100 feet, voltage drop usually pushes it up a size or two — run the numbers above for your actual length.
Does voltage drop or ampacity decide the wire size?
Whichever demands the larger conductor. Ampacity governs on short runs, voltage drop governs on long ones, and the crossover is usually somewhere around 100 to 150 feet. Both have to be satisfied.
What is an acceptable voltage drop?
Three percent on a branch circuit and five percent total from the service to the load, combining feeder and branch. These come from informational notes in NEC 210.19 and 215.2 — they are strong guidance rather than an enforceable limit in most jurisdictions.
How do I calculate voltage drop?
For single phase, VD = 2 × K × amps × one-way feet ÷ circular mils, where K is 12.9 for copper and 21.2 for aluminium. For three phase, replace the 2 with 1.732. Circular mils come from NEC Chapter 9, Table 8.
Why do I have to derate for conductor count?
Conductors bundled in a raceway heat each other and have nowhere to shed that heat. NEC 310.15(C)(1) multiplies ampacity by 0.8 for four to six current-carrying conductors, 0.7 for seven to nine, and 0.5 for ten to twenty. Ambient temperature derating multiplies on top of it.
Is aluminium wire acceptable?
Yes for feeders and services, and it is standard practice for service entrance conductors. Aluminium carries roughly two thirds of copper's ampacity for the same size, so you go up about two sizes, and every termination has to be rated for aluminium and treated with antioxidant compound.