Duct Size Calculator
Enter the airflow and your target friction rate and this calculator returns the round duct diameter required, the equivalent rectangular dimensions, and the air velocity that results. Velocity is checked against the usual limits for the type of run you are sizing.
400 CFM per ton is the standard design airflow. Enter tons if you prefer.
The dimension you are constrained by — joist bay depth, soffit height. Ignored for round.
0.1 is the residential convention. Lower means bigger, quieter duct.
- Velocityabove 700 fpm — expect noise, go up a size
- 733fpm
- Airflow1.00 tons at 400 CFM per ton
- 400CFM
- Calculated diameterbefore rounding to stock size, galvanised sheet metal
- 9.83in
- Equivalent round diameter
- 10in
- Rectangular equivalentsame friction loss as the round size above
- 8 × 11in
- Cross-sectional area
- 0.545sq ft
What this figure includes
Diameter comes from the standard friction-loss equation for galvanised round duct, with a roughness allowance for other materials, then rounded up to a stock size. It sizes one duct section at the friction rate you enter. It does not perform a whole-system Manual D: it does not add equivalent lengths for elbows, takeoffs, boots and transitions, calculate total external static pressure against the blower curve, balance a trunk-and-branch system, or account for filter, coil and register losses. Have a mechanical contractor confirm the system design.
How this is calculated
The friction-rate method
Duct sizing is not about squeezing air through the smallest pipe that will take it. It is about picking how much pressure you are willing to spend per hundred feet of duct, and then sizing every section to spend it at the same rate.
That number is the friction rate, in inches of water gauge per 100 feet. The residential convention is 0.1 in.w.g. per 100 ft, and it exists because it produces velocities that are quiet and duct sizes that fit in a house. Size everything at the same friction rate and the system self-balances: air divides itself between branches roughly in proportion to their capacity, because each path costs the same per foot.
The underlying relationship, for galvanised round duct, is:
Δp = 0.109136 × Q^1.9 ÷ D^5.02
where Δp is inches w.g. per 100 ft, Q is CFM and D is diameter in inches. Rearranged for what you actually want:
D = (0.109136 × Q^1.9 ÷ Δp)^(1/5.02)
Note that exponent of 5.02 on the diameter. Duct resistance is extraordinarily sensitive to size — a small increase in diameter buys a large reduction in pressure loss. Going from 6 in to 7 in, a 17% increase, cuts the friction loss by more than half.
A worked example
A branch run carrying 400 CFM — one ton of cooling at the standard 400 CFM per ton — in galvanised round duct at 0.1 in.w.g. per 100 ft.
- Q^1.9 = 400^1.9 = 88,000
- 0.109136 × 88,000 = 9,604
- 9,604 ÷ 0.1 = 96,040
- D = 96,040^(1/5.02) = 9.83 inches
Round up to the stock 10 in. Check the velocity:
- Area = π × 5² ÷ 144 = 0.545 sq ft
- Velocity = 400 ÷ 0.545 = 733 fpm
That is right at the top of the comfortable range for a branch feeding a bedroom register, and a fraction over the 700 fpm most designers hold to. Squeeze the same 400 CFM into 8 in round and the calculation says you are running at 0.19 in.w.g. per 100 ft and 1,146 fpm — nearly twice the friction and audible in a quiet room. That is the trade-off in one example: friction rate sets size, size sets velocity, and velocity sets noise.
Velocity is a noise specification
Air makes noise moving through duct, and the noise rises sharply with velocity. The working limits:
- Branch runs to bedrooms and living spaces: 500–700 fpm. Above about 750 you hear it, and above 900 people complain.
- Supply trunks and mains: 700–900 fpm. They are usually in an attic, crawl or basement, so a little more noise is tolerable, and the runs are short.
- Returns: 500–700 fpm. Return grilles are often in a hallway at head height, so they are the most audible part of the system and the most commonly undersized.
- Mechanical rooms and commercial mains: 1,000–1,500 fpm is normal, because nobody is trying to sleep next to it.
Velocity too low is also a fault, though a rarer one. Below about 400 fpm supply air fails to throw across the room from the register and dumps straight down the wall, which people experience as a cold draught in one spot and a stuffy room everywhere else.
Equivalent round diameter for rectangular duct
Rectangular duct is not sized by matching cross-sectional area — that gets it wrong, because a flat duct has far more wall surface per unit of air and therefore more friction. The correct conversion is the equivalent round diameter:
De = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25
where a and b are the rectangular dimensions in inches. A rectangular duct has the same pressure loss as the round duct whose diameter equals its De.
The practical consequence: aspect ratio costs you. A 8 × 8 square duct has a De of 8.7 in. Flatten it to 4 × 16 — same 64 square inches — and the De drops to 8.3 in, so it carries less air for the same pressure. Push it to 3 × 22 and it falls further still. Keep the aspect ratio under about 4:1 where you can, and treat every extra bit of flattening as a real loss you are paying for in blower power, not a free way to fit duct into a joist bay.
What this does not cover
This sizes duct sections. It does not size a system. A real design — Manual D — starts by measuring the available static pressure at the blower, subtracts the filter, coil, registers and grilles, divides what is left by the total effective length of the longest run including every fitting's equivalent length, and only then arrives at the friction rate to size with. An elbow can be worth 25 feet of straight duct, a boot more. On a badly laid out system the fittings dominate.
Two more things worth stating plainly: flexible duct only performs near these numbers when it is pulled taut and fully supported, and a compressed or sagging flex run can lose several times its rated pressure per foot. And any duct outside the conditioned envelope should be sealed with mastic and insulated — leaky attic duct routinely throws away twenty to thirty percent of the system's capacity before the air reaches a room.
Frequently asked questions
- What size duct do I need for 400 CFM?
- About 7.1 inches at the standard 0.1 in.w.g. per 100 ft friction rate, so an 8 inch round duct. If it is a branch feeding a bedroom, size down the friction rate to keep velocity under 700 fpm, which pushes it to 10 inch.
- How many CFM per ton of air conditioning?
- Four hundred CFM per ton is the design standard. High-humidity climates sometimes design at 350 CFM per ton to get more moisture removal, and dry climates occasionally run 450.
- What friction rate should I use for residential duct?
- 0.1 inches water gauge per 100 feet is the convention, and it produces sizes and velocities that work in a house. A proper Manual D derives the rate from the available static pressure and the total effective length rather than assuming it.
- What is the maximum air velocity in a duct?
- About 700 fpm in branches to living spaces, 900 in supply trunks, and 1,500 in mechanical rooms or commercial mains. Above those figures the duct becomes audible, and return grilles at head height are the worst offenders.
- How do I convert round duct to rectangular?
- Use equivalent round diameter: De = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25. Do not match cross-sectional area — a flat duct has more wall surface and more friction, so equal area carries less air.
- Is flexible duct as good as metal?
- Only when it is pulled fully taut and properly supported, and even then it has slightly more resistance than smooth metal. Compressed or sagging flex can cost several times its rated pressure per foot and is one of the most common causes of a weak register.
Related calculators
- BTU CalculatorEstimate the BTU per hour and tonnage a room or house needs from size, climate, insulation…
- HVAC Replacement Cost CalculatorEstimate AC, heat pump or mini-split replacement cost by tonnage, SEER2 tier and ductwork.…
- Insulation CalculatorWork out batts, bags or board feet and the R-value you will actually achieve in the cavity…
- Wire Size CalculatorSize a conductor by both ampacity and voltage drop, with derating for heat and conductor c…
- Conduit Fill CalculatorCheck conduit fill against NEC Chapter 9 limits and find the smallest size that passes. Fr…